Fire suppression Systems
Autonomous fire suppression system Impulse-BS
An autonomous system of local application SPGAU gaseous fire “Impulse-BS”. BS – means BOX SAFE!
Operating temperature in the protected volume: -10° to + 60°C Extinguishing fire class A2, B, and electrical equipment under voltage up to 1000 V Type of extinguishing agent – HFC-125 (0.9 to 4.5kg), HFC-227ea (1.1 to 5.5 kg).Operating pressure at 20°C-16bar. Low self-destruction thermosensitive tube Brand DeTec – 80±10°C Configuration (depends on a model): 1.0-5.0 L liter bottle (cylinder), locking and starting device with ball valve, siphon tube, a pressure gauge with a pressure switch, a safety membrane fitting Brand DeTec tube, a tube Brand DeTec – 5.0-10.0 m length, PG inlet gland for pipe mounting for tube – 20 pcs., tube cap, cylinder mounting bracket, label, passport (combined with the manual), carton tare.
Structurally Impulse-BS is a bottle of cylindrical form with a shut-off and starting system (S&SS), filled with a gas extinguishing agent (HFC Fluorinated Hydrocarbons).
The neck of the bottle by means of a threaded connection is established with a safety device S&SS, membrane and a pressure gauge (with built-in pressure switch). Through the fitting clamp, to a S&SS-ball valve, goes a connected thermosensitive tube –“Brand DeTec”, with the corresponding diameter, and finishing cap. To fix a module “Impulse-BS” and thermosensitive tube together, use an appropriate bracket.
Fire fighting in facilities of server cabinets, telecommunications equipment, instrument and electrical enclosures, cabinets with flammable liquids storage cabinets securities, other electronic and technological equipment. SPGAU “Impulse-BS” designed for long-term storage under pressure and release into protected volume an HFC agent, extinguishing fires of class A2, B, and electrical equipment under voltage. The role of gas-propellant is played by clear nitrogen.
Identification | Measurement | Type of module | |||
Impulse-BS-1 | Impulse-BS-1.5 | Impulse-BS-3 | Impulse-BS-5 | ||
Cylinder capacity | liter | 1.0+0.10 | 1.5+0.15 | 3.0+0.30 | 5.0+0.50 |
Maximal cylinder loading (HFC125/HFC227ea) | kg | 0.9/1.1 | 1.35 / 1.65 | 2.7/3.3 | 4.5/5.5 |
Maximal protection volume for conditionally sealed space with leakage parameter -0.01 m-1 (HFC125/HFC227ea) | m3 | 1.2 / 1.48 | 1.8 / 2.23 | 3.6 / 4.46 | 6.0 / 7.43 |
Maximal protection volume for sealed space with leakage parameter 0.01-0,044 m-1 (HFC125/HFC227ea) | m3 | 1.15 / 1.5 | 1.6 / 2.05 | 2.5 / 3.2 | 3.95 / 4.7 |
Working pressure (Pw), temp (20±2Co) | bar | 16,0± 0,5 | |||
Estimated pressure (Pf), ext. temp (50±2Co) | bar | 26,0± 2,0 | |||
Tested pressure for cylinder, max, | bar | 60,0+0,5 | |||
Self-activated fuse membrane pressure | bar | 50,0 ± 5 | |||
Time for extinguish agent release, max | sec | 10 | 15 | 30 | 40 |
Net weight, max | kg | 4,0 ± 0,10 | 5,5± 0,15 | 9,5± 0,20 | 11,5 ± 0,30 |
Dimensions: – height – diameter | mm | 502 76 | 411 114 | 586 114 | 819 114 |
Working temperature range | oC | -10 + 50 | |||
Detection tube “Brand DeTec” normal length | m | 5.0 | 5.0 | 7.0 | 10.0 |
Activation resource, not less than | Times | 5 | |||
Working Lifetime, not less than | Years | 10 | |||
Parameters of the circuit pressure switch | |||||
The activation pressure of the pressure switch | Bar | 2,0 ± 0,5 | |||
The voltage at DC terminals pressure switch | V | 30 | |||
Amperage, max | A | 0,3 | |||
«Brand DeTect» thermosensitive tube features | |||||
The temperature for outlet formation: - For the tube Ø10 mm (TRN 10/8) - For the tube Ø 8 mm (TRN 8/6) |
° C
|
80 ± 10 100± 10 | |||
Operating temperature range: - For the tube Ø 10 mm (TRN 10/8) - For the tube Ø 8 mm (TRN 8/6) |
° C
|
-10 + 60 -10 + 80 | |||
Colour of material | red |